Konfigurieren/Status Alarm Profile | ||
Test Kennung: | 1.3.6.1.4.1.25623.1.0.801622 |
Kategorie: | Buffer overflow |
Titel: | RealWin SCADA System <= 2.1 Build 6.1.10.10 Multiple Buffer Overflow Vulnerabilities |
Zusammenfassung: | RealWin SCADA system is prone to multiple buffer overflow; vulnerabilities. |
Beschreibung: | Summary: RealWin SCADA system is prone to multiple buffer overflow vulnerabilities. Vulnerability Insight: The flaws are due to a boundary error when processing 'SCPC_INITIALIZE', 'SCPC_INITIALIZE_RF' and 'SCPC_TXTEVENT' packets that can be exploited to cause a stack-based buffer overflow by sending specially crafted packets to port 912/TCP. Vulnerability Impact: Successful exploitation may allow remote attackers to execute arbitrary code on the system or cause a denial of service condition. Affected Software/OS: RealWin SCADA System 2.0 Build 6.1.8.10 and prior. Solution: Update to version 2.1 Build 6.1.10.10 or later. CVSS Score: 10.0 CVSS Vector: AV:N/AC:L/Au:N/C:C/I:C/A:C |
Querverweis: |
Common Vulnerability Exposure (CVE) ID: CVE-2010-4142 BugTraq ID: 44150 http://www.securityfocus.com/bid/44150 http://www.exploit-db.com/exploits/15259 http://www.exploit-db.com/exploits/15337 http://aluigi.org/adv/realwin_1-adv.txt http://secunia.com/advisories/41849 |
Copyright | Copyright (C) 2010 Greenbone AG |
Dies ist nur einer von 145615 Anfälligkeitstests in unserem Testpaket. Finden Sie mehr über unsere vollständigen Sicherheitsüberprüfungen heraus. Um einen gratis Test für diese Anfälligkeit auf Ihrem System durchlaufen zu lassen, registrieren Sie sich bitte unten. |